Laboratory verification of system for grid connection of a 12 kW variable speed wind turbine with a permanent magnet synchronous generator

Titel: Laboratory verification of system for grid connection of a 12 kW variable speed wind turbine with a permanent magnet synchronous generator
Författare:
Senad Apelfröjd, Fredrik Bülow, Jon Kjellin, Sandra Eriksson
Utgivare:
Wind Energy
Årtal:
2011
Ämnesord: VAWT, Tap transformer, LCL-filter, voltage source inverter
Rapport via DIVA



Sammanfattning/Abstract:

In this paper the first laboratory tests of the gridconnection system, connected to a resistiveload, for a vertical axis wind turbine (VAWT)with a permanent magnet generator arepresented. The system is based on a taptransformertopology with a voltage sourceinverter and an LCL-filter. The use of a taptransformer topology eliminates the need for aDC-DC converter to handle the variations inDC voltage. The harmonic content of thecurrents from experiments and simulationsperformed in Simulink using different taps onthe transformer are presented. The simulatedcurrents, fed to the resistive load, have a totalharmonic distortion (THD) of 0.5% to 0.9% forthe different taps. The experimental systemhas a current THD ranging from 1.8% to 2.8%.The difference is expected to be due tounbalances, delays and dead times in theexperimental set-up as the major THDcontribution is from harmonic orders below 11.The results show that an LCL filter can bedesigned to meet the demands on powerquality for grid connection of the system withall the taps of the tap transformer inaccordance with IEEE 519-1992.